NFPA 30
Flammable and Combustible Liquids Code

Published: 2012
Format: Book
Status: Active
Order #: 3012

Price: $48.50

 

Current Edition: 2012    Next Edition: 2014

1.1 Scope.
1.1.1* This code shall apply to the storage, handling, and use of flammable and combustible liquids, including waste liquids, as herein defined and classified.
1.1.2 This code shall not apply to the following:
(1)* Any liquid that has a melting point of 100°F (37.8°C) or greater
(2)* Any liquid that does not meet the criteria for fluidity given in the definition of liquid in Chapter 3 and in the provisions of Chapter 4
(3) Any cryogenic fluid or liquefied gas, as defined in Chapter 3
(4)* Any liquid that does not have a flash point, but which is capable of burning under certain conditions
(5)* Any aerosol product
(6) Any mist, spray, or foam
(7)* Transportation of flammable and combustible liquids as governed by the U.S. Department of Transportation
(8)* Storage, handling, and use of fuel oil tanks and containers connected with oil-burning equipment

A.1.1.1 This code is recommended for use as the basis for legal regulations. Its provisions are intended to reduce the hazard to a degree consistent with reasonable public safety, without undue interference with public convenience and necessity, of operations that require the use of flammable and combustible liquids. Compliance with this code does not eliminate all hazards in the use of flammable and combustible liquids. (See the Flammable and Combustible Liquids Code Handbook for additional explanatory information.)
A.1.1.2(1) Liquids that are solid at 100°F (37.8°C) or above, but are handled, used, or stored at temperatures above their flash points, should be reviewed against pertinent sections of this code.
A.1.1.2(2) The information in
A.1.1.2(1) also applies here.
A.1.1.2(4) Certain mixtures of flammable or combustible liquids and halogenated hydrocarbons either do not exhibit a flash point using the standard closed-cup test methods or will exhibit elevated flash points. However, if the halogenated hydrocarbon is the more volatile component, preferential evaporation of this component can result in a liquid that does have a flash point or has a flash point that is lower than the original mixture. In order to evaluate the fire hazard of such mixtures, flash point tests should be conducted after fractional evaporation of 10, 20, 40, 60, or even 90 percent of the original sample or other fractions representative of the conditions of use. For systems such as open process tanks or spills in open air, an open-cup test method might be more appropriate for estimating the fire hazard.
A.1.1.2(5) See NFPA 30B, Code for the Manufacture and Storage of Aerosol Products.
A.1.1.2(7) Requirements for transportation of flammable and combustible liquids can be found in NFPA 385, Standard for Tank Vehicles for Flammable and Combustible Liquids, and in the U.S. Department of Transportation’s Hazardous Materials Regulations, Title 49, Code of Federal Regulations, Parts 100–199. A.1.1.2(8) See NFPA 31, Standard for the Installation of Oil-Burning Equipment .

 

About NFPA

The world's leading advocate of fire prevention and an authoritative source on public safety, NFPA develops, publishes, and disseminates more than 300 consensus codes and standards intended to minimize the possibility and effects of fire and other risks.

The mission of NFPA is to reduce the burden of fire and other hazards!

Customer Service - ILS
At International Library Service, we are happy to be of service to you!

Site produced and maintained by International Library Service * 889 N. Freedom Blvd., Suite 100; Provo, Utah 84604
Copyright 1998 - 2009. All rights reserved.